ACS550 User’s Manual
125
Start-Up
4016
ACT1 INPUT
Defines the source for actual value 1 (
ACT
1).
0 =
AI
1 – Uses analog input 1 for
ACT
1.
1 =
AI
2 – Uses analog input 2 for
ACT
1.
2 = Current – Uses current for
ACT
1, scaled so:
• Min
ACT
1 = 0 current
• Max
ACT
1 = 2 x nominal current
3 = Torque – Uses torque for
ACT
1, scaled so:
• Min
ACT
1 = -2 x nominal torque
• Max
ACT
1 = 2 x nominal torque
4 = Power – Uses power for
ACT
1, scaled so:
• Min
ACT
1 = -2 x nominal power
• Max
ACT
1 = 2 x nominal power
4017
ACT2 INPUT
Defines the source for actual value 2 (
ACT
2).
0 =
AI
1 – Uses analog input 1 for
ACT
2.
1 =
AI
2 – Uses analog input 2 for
ACT
2.
2 = Current – Uses current for
ACT
2, scaled so:
• Min
ACT
2 = 0 current
• Max
ACT
2 = 2 x nominal current
3 = Torque – Uses torque for
ACT
2, scaled so:
• Min
ACT
2 = -2 x nominal torque
• Max
ACT
2 = 2 x nominal torque
4 = Power – Uses power for
ACT
2, scaled so:
• Min
ACT
2 = -2 x nominal power
• Max
ACT
2 = 2 x nominal power
4018
ACT1 MINIMUM
Sets the minimum value for
ACT
1.
• Used with analog input min/max settings (e.g. 1301
MINIMUM
AI
1,
1302
MAXIMUM
AI
1).
• Scales analog inputs used as actual values.
• See figure: A= Normal; B = Inversion (
ACT
1
MINIMUM
>
ACT
1
MAXIMUM
)
4019
ACT1 MAXIMUM
Sets the maximum value for
ACT
1.
• See 4018
ACT
1
MINIMUM
.
4020
ACT2 MINIMUM
Sets the minimum value for
ACT
2.
• See 4018
ACT
1
MINIMUM
.
4021
ACT2 MAXIMUM
Sets the maximum value for
ACT
2.
• See 4018
ACT
1
MINIMUM
.
Code Description
Analog input signal
P 4019
P 4018
P 1301
P 1302
P 1301
P 1302
P 4018
P 4019
ACT
1 (%)
Analog input signal
ACT
1 (%)
A
B