0139
PROCESS VAR 3
Process variable 3
• Defined by parameters in Group 34: Panel Display / Process Variables.
0140
RUN TIME
The drive’s accumulated running time in thousands of hours (kh).
0141
MWH COUNTER
The drive’s accumulated power consumption in megawatt hours. Can not be reset.
0142
REVOLUTION CNTR
The motor’s accumulated revolutions in millions of revolutions.
0143
DRIVE ON TIME (HI)
The drive’s accumulated power on time in days.
0144
DRIVE ON TIME (LO)
The drive’s accumulated power on time in 2 second ticks (30 ticks = 60 seconds).
0145
MOTOR TEMP
Motor temperature in degrees centigrade / PTC resistance in Ohms.
• Applies only if motor temperature sensor is set up. See parameter 3501.
0146
…
0148
If used, see appropriate accessory documentation.
Code Description