ACS550 User’s Manual
107
Start-Up
3023
WIRING FAULT
Defines the drive response to cross wiring faults and to ground faults detected when the drive is NOT running. When
the drive is not running it monitors for:
• Improper connections of input power to the drive output (the drive can display fault 35,
OUTPUT
WIRING
if improper
connections are detected).
• Ground faults (the drive can display fault 16,
EARTH
FAULT
if a ground fault is detected). Also, see parameter 3017
EARTH
FAULT
.
0 =
DISABLE
– No drive response to either of the above monitoring results.
1 =
ENABLE
– The drive displays faults when this monitoring detects problems.
Code Description