ACS550 User’s Manual
101
Start-Up
Group 26: Motor Control
Code Description
2601
FLUX OPTIMIZATION
Changes the magnitude of the flux depending on the actual load. Flux Optimization can reduce the total energy
consumption and noise, and should be enabled for drives that usually operate below nominal load.
0 = Disables the feature.
1 = Enables the feature.
2602
FLUX BRAKING
Provides faster deceleration by raising the level of
magnetization in the motor when needed, instead of
limiting the deceleration ramp. By increasing the flux in
the motor, the energy of the mechanical system is
changed to thermal energy in the motor.
0 = Disables the feature.
1 = Enables the feature.
2603
IR COMP VOLT
Sets the IR compensation voltage used for 0 Hz.
• Requires parameter 9904
MOTOR
CTRL
MODE
= 3
(
SCALAR
:
SPEED
).
• Keep IR compensation as low as possible to prevent
overheating.
• Typical IR compensation values are:
IR Compensation
• When enabled, IR Compensation provides an extra
voltage boost to the motor at low speeds. Use IR
Compensation, for example, in applications that require a
high breakaway torque.
2604
IR COMP FREQ
Sets the frequency at which IR compensation is 0 V (in
% of motor frequency).
2605
U/f RATIO
Selects the form for the U/f (voltage to frequency) ratio below field weakening point.
1 =
LINEAR
– Preferred for constant torque applications.
2 =
SQUARE
– Preferred for centrifugal pump and fan applications. (Square is more silent for most operating
frequencies.)
2606
SWITCHING FREQ
Sets the switching frequency for the drive. Also see parameter 2607
SW
FREQ
CTRL
Derating" on page 217.
• Higher switching frequencies mean less noise.
• The 12 kHz switching frequency is available only if parameter 9904
MOTOR
CTRL
MODE
= 3 (
SCALAR
:
SPEED
).
• The 12 kHz switching frequency is available only on frame sizes R1…R6
120%
80
40
0
W/O Flux Braking
50
With Flux Braking
5
10
20
30
40
120%
80
40
0
50
5
10
20
30
40
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
2.2 kW
15 kW
37 kW
75 kW
250 kW
Rated Motor Power
Braking
f (Hz)
f (Hz)
Torque (%)
380…480 V Units
P
N
(kW)
3
7.5
15
37
132
IR comp (V)
18
15
12
8
3
Motor
f (Hz)
A
B
Voltage
A = IR Compensated
B = No compensation
P 2603
P 2604