42
ACS550 User’s Manual
Start-Up
Application Macros
Macros change a group of parameters to new, predefined values. Use macros to
minimize the need for manual editing of parameters. Selecting a macro sets all other
parameters to their default values, except:
•
Group 99: Start-up Data parameters (except parameter 9904)
•
The
PARAMETER
LOCK
1602
•
The
PARAM
SAVE
1607
•
The
COMM
FAULT
FUNC
3018 and
COMM
FAULT
TIME
3019
•
The
COMM
PROT
SEL
9802
•
Groups 50…53 parameters
•
Group 29 Maintenance triggers
After selecting a macro, additional parameter changes can be made manually using
the control panel.
Application macros are enabled by setting the value for parameter 9902
APPLIC
MACRO
. By default, 1, ABB Standard, is the enabled macro.
The following sections describe each of the application macros and provide a
connection example for each macro.
The last section below, "Macro Default Values for Parameters" lists the parameters
that the macros change, and the default values established by each macro.