![ABB ACS550-01 Скачать руководство пользователя страница 15](http://html.mh-extra.com/html/abb/acs550-01/acs550-01_user-manual_2977015.webp)
ACS550 User’s Manual
15
Installation
Power Connection Diagrams
The following diagram shows the terminal layout for frame size R3, which, in
general, applies to frame sizes R1
…
R6, except for the R5/R6 power and ground
terminals.
Warning! For floating, impedance grounded, or unsymmetrically grounded
networks, disconnect the internal RFI filter by removing:
- On ACS550-01: screws EM1 and EM3.
- On ACS550-U1: screw EM1 (drive is shipped with EM3 already removed).
See "Floating Networks" on page 222.
Panel Connector
Power LED (Green)
Fault LED (Red)
Optional Module 1
J2 – DIP Switch
X1 – Communications
Optional Module 2
GND
Power Output to Motor
Power Input
EM1
X1 – Analog Inputs and Outputs
X1 – Digital Inputs
X1 – Relay Outputs
J2
ON
off position
on position
for RS485 Termination
(and 10 V Ref. Voltage Output)
(and 24 V Aux. Voltage Output)
EM3
PE
(U1, V1, W1)
(U2, V2, W2)
Optional braking
Frame
Size
Terminal
Labels
Brake Options
R1, R2 BRK+, BRK-
Brake resistor
R3, R4 UDC+, UDC- • Braking unit
• Chopper and resistor
X0003
(RS485)
R5/R6 differ.
See
Frame Sizes
next page.
Diagram shows the R3 frame.
J2
ON
Other frames have similar layouts.
J1 – DIP Switches for Analog Inputs
J1
AI1: (in Voltage Position)
AI2: (in Current Position)
ON
ON