FAULT WORD 1
Read-only copy of the Fault Word 1.
• When a fault is active, the
corresponding bit for the active fault
is set in the Fault Words.
• Each fault has a dedicated bit
allocated within Fault Words.
• See "Fault Listing" on page 201 for a
description of the faults.
• The control panel displays the word
in hex. For example, all zeros and a 1
in Bit 0 displays as 0001. All zeros
and a 1 in Bit 15 displays as 8000.
0306
FAULT WORD 2
Read-only copy of the Fault Word 2.
• See parameter 0305.
0307
FAULT WORD 3
Read-only copy of the Fault Word 3.
• See parameter 0305.
0308
ALARM WORD 1
• When an alarm is active, the
corresponding bit for the active alarm
is set in the Alarm Words.
• Each alarm has a dedicated bit
allocated within Alarm Words.
• Bits remain set until the whole alarm
word is reset. (Reset by writing zero
to the word.)
• The control panel displays the word
in hex. For example, all zeros and a 1
in Bit 0 displays as 0001. All zeros
and a 1 in Bit 15 displays as 8000.
0309
ALARM WORD 2
See parameter 0308.
Bit #
0305,
FAULT
WORD
1 0306,
FAULT
WORD
2
0307,
FAULT
WORD
3
0
OVERCURRENT
UNDERLOAD EFB
1
1
DC OVERVOLT
THERM FAIL
EFB 2
2
DEV OVERTEMP
OPEX LINK
EFB 3
3
SHORT CIRC
OPEX PWR
Incompatible software
type
4
Reserved CURR
MEAS
Reserved
5
DC UNDERVOLT
SUPPLY PHASE
Reserved
6
AI1 LOSS
ENCODER ERROR Reserved
7
AI2 LOSS
OVERSPEED
Reserved
8 MOT
OVERTEMP Reserved
Reserved
9
PANEL LOSS
DRIVE ID
Reserved
10 ID RUN FAIL
CONFIG FILE
System error
11 MOTOR STALL
SERIAL 1 ERR
System error
12 Reserved
EFB CON FILE
System error
13 EXT FLT 1
FORCE TRIP
System error
14 EXT FLT 2
MOTOR PHASE
Hardware error
15
EARTH FAULT
OUTPUT WIRING
Param. setting fault
Bit #
0308,
ALARM
WORD
1
0309,
ALARM
WORD
2
0
OVERCURRENT
Reserved
1
OVERVOLTAGE
PID SLEEP
2
UNDERVOLTAGE
ID RUN
3
DIRLOCK Reserved
4
I/O COMM
START ENABLE 1 MISSING
5
AI1 LOSS
START ENABLE 2 MISSING
6
AI2 LOSS
EMERGENCY STOP
7
PANEL LOSS
ENCODER ERROR
8
DEVICE OVERTEMP
FIRST START
9
MOT OVERTEMP
Reserved
10
UNDERLOAD Reserved
11
MOTOR STALL
Reserved
12
AUTORESET Reserved
13
PFC AUTOCHANGE
Reserved
14
PFC INTERLOCK
Reserved
15
Reserved
Reserved