![ABB ACS550-01 Скачать руководство пользователя страница 70](http://html.mh-extra.com/html/abb/acs550-01/acs550-01_user-manual_2977070.webp)
70
ACS550 User’s Manual
Start-Up
Group 03: FB Actual Signals
This group monitors fieldbus communications.
Code Description
0301
FB CMD WORD 1
Read-only copy of the Fieldbus
Command Word 1.
• The fieldbus command is the
principal means for controlling the
drive from a fieldbus controller. The
command consists of two Command
Words. Bit-coded instructions in the
Command Words switch the drive
between states.
• To control the drive, using the
Command Words, an external
location (
EXT
1 or
EXT
2) must be
active and set to
COMM
. (See
parameters 1001 and 1002.)
• The control panel displays the word
in hex. For example, all zeros and a 1
in Bit 0 displays as 0001. All zeros
and a 1 in Bit 15 displays as 8000.
0302
FB CMD WORD 2
Read-only copy of the Fieldbus
Command Word 2.
• See parameter 0301.
0303
FB STS WORD 1
Read-only copy of the Status Word 1.
• The drive sends status information to
the fieldbus controller. The status
consists of two Status Words.
• The control panel displays the word
in hex. For example, all zeros and a 1
in Bit 0 displays as 0001. All zeros
and a 1 in Bit 15 displays as 8000.
0304
FB STS WORD 2
Read-only copy of the Status Word 2.
• See parameter 0303.
Bit #
0301,
FB
CMD
WORD
1
0302,
FB
CMD
WORD
2
0
STOP
Reserved
1
START
Reserved
2
REVERSE
Reserved
3
LOCAL
Reserved
4
RESET
Reserved
5
EXT2
Reserved
6
RUN_DISABLE
Reserved
7
STPMODE_R
Reserved
8
STPMODE_EM Reserved
9
STPMODE_C
Reserved
10
RAMP_2
Reserved
11
RAMP_OUT_0
REF_CONST
12
RAMP_HOLD
REF_AVE
13
RAMP_IN_0
LINK_ON
14
RREQ_LOCALLOC
REQ_STARTINH
15
TORQLIM2
OFF_INTERLOCK
Bit #
0303,
STS
CMD
WORD
1
0304,
FB
STS
WORD
2
0
READY
ALARM
1
ENABLED
REQ_MAINT
2
STARTED
DIRLOCK
3
RUNNING
LOCALLOCK
4
ZERO_SPEED
CTL_MODE
5
ACCELERATE
Reserved
6
DECELERATE
Reserved
7
AT_SETPOINT
Reserved
8
LIMIT
Reserved
9
SUPERVISION
Reserved
10
REV_REF
REQ_CTL
11
REV_ACT
REQ_REF1
12
PANEL_LOCAL
REQ_REF2
13
FIELDBUS_LOCAL
REQ_REF2EXT
14
EXT2_ACT
ACK_STARTINH
15
FAULT
ACK_OFF_ILCK