8
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation
GS 05P02D41-01EN Mar.14,2016-00
Safety and EMC Standards
• Safety:
Compliant with IEC/EN 61010-1 (CE), IEC/EN 61010-
2-201 (CE), IEC/EN 61010-2-030 (CE), approved by
CAN/CSA C22.2 No. 61010-1 (CSA), approved by UL
61010-1.
Installation category: II
Pollution degree: 2
Measurement category: I (CAT I) (UL, CSA)
O (Other) (CE)
Rated measurement input voltage: Max. 10 V DC
Rated transient overvoltage: 1500 V (
*
)
*:
This is a reference safety standard value for
measurement category I of CSA/UL 61010-1, and
for measurement category O of IEC/EN 61010-2-
030. This value is not necessarily a guarantee of
instrument performance.
• EMC standards:
Compliant with
CE marking
EN 61326-1 Class A, Table 2 (For use in industrial
locations),
EN 61326-2-3
*: The instrument continues to operate at a
measurement accuracy of within ±20% of the
range during testing.
EN 55011 Class A, Group 1
EN 61000-3-2 Class A
EN 61000-3-3
EMC Regulatory Arrangement in Australia and New Zealand
EN 55011 Class A, Group 1
• KC marking: Electromagnetic wave interference
prevention standard, electromagnetic wave protection
standard compliance
Construction, Installation, and Wiring
• Dust-proof and drip-proof: IP66 (for front panel) (Not
available for side-by-side close mounting)/NEMA4 *
*:
Hose-down test only
• Material: Polycarbonate (Flame retardancy: UL94V-0)
• Case color: White (Light gray) or Black (Light
charcoal gray)
• Weight: 0.5 kg or less
• External dimensions (mm):
UP35A: 96 (W) × 96 (H) × 65 (depth from the panel
face)
UP32A: 48 (W) × 96 (H) × 65 (depth from the panel
face)
(Depth except the projection on the rear panel)
• Installation: Direct panel mounting; mounting bracket,
one each for upper and lower mounting
• Panel cutout dimensions (mm):
UP35A: 92
+0.8/0
(W) × 92
+0.8/0
(H)
UP32A: 45
+0.6/0
(W) × 92
+0.8/0
(H)
•
Mounting attitude: Up to 30 degrees above the
horizontal. No downward titling allowed.
• Wiring: M3 screw terminal with square washer (for
signal wiring and power wiring)
Power Supply Specifications and Isolation
• Power supply:
Rated voltage: 100-240 V AC (+10%/-15%), 50/60 Hz
24 V AC/DC (+10%/-15%) (for /DC option)
• Power consumption:
UP35A: 18 VA (DC: 9 VA, AC: 14 VA if /DC option is
specified)
UP32A: 15 VA (DC: 7 VA, AC: 11 VA if /DC option is
specified)
• Data backup: Nonvolatile memory
• Power holdup time: 20 ms (for 100 V AC drive)
• Withstanding voltage
Between primary terminals and secondary terminals:
2300 V AC for 1 minute (UL, CSA)
Between primary terminals and secondary terminals:
3000 V AC for 1 minute (CE)
Between primary terminals: 1500 V AC for 1 minute
Between secondary terminals: 500 V AC for 1 minute
(Primary terminals: Power* and relay output
terminals; Secondary terminals: Analog I/O signal
terminals, contact input terminals, communication
terminals and functional grounding terminals.)
*:
Power terminals for 24V AC/DC models are the
secondary terminals.
• Insulation resistance: Between power supply
terminals and a grounding terminal 20 MΩ or more at
500 V DC
• Isolation specifications
PV (universal ) input terminals
Control relay (contact point c/contact point a x 2) output terminals
PV event-1 relay (contact point a) output terminals
PV event-2 relay (contact point a) output terminals
Time event-1 relay (contact point a) output terminals
Position proportional relay output terminals
Contact input terminals (all)
RS-485 communication terminals
24 V DC loop power supply terminals
Contact output (transistor) terminals
Ethernet communication terminal
PROFIBUS-DP/DeviceNet/CC-Link communication terminals
Current transformer input terminals
Control, retransmission (analog) output terminals
(not isolated between the analog output terminals)
Valve position (feedback) input terminals
Internal
circuits
Power
supply
The circuits divided by lines are insulated mutually.
Environmental Conditions
Normal Operating Conditions:
• Ambient temperature: -10 to 50ºC (side-by-side close
mounting: -10 to 40 ºC)
If the CC-Link option is specified, 0 to 50 °C for
UP35A; 0 to 40 °C for UP32A.
(side-by-side mounting: 0 to 40 °C for UP35A/UP32A
with CC-Link option)
• Ambient humidity: 20 to 90% RH (no condensation
allowed)
• Magnetic field: 400 A/m or less
• Continuous vibration at 5 to 9 Hz: Half amplitude of
1.5 mm or less, 1oct/min for 90 minutes each in the
three axis directions
Continuous vibration at 9 to 150 Hz: 4.9 m/s
2
or
less, 1oct/min for 90 minutes each in the three axis
directions
• Short-period vibration: 14.7 m/s
2
, 15 seconds or less
• Shock: 98 m/s
2
or less, 11 ms
• Altitude: 2000 m or less above sea level
• Warm-up time: 30 minutes or more after the power is
turned on
• Startup time: Within 10 seconds
*:
The LCD (a liquid crystal display) is used for a
display portion of this product. The LCD has a
characteristic that the display action becomes
late at the low temperature. However, the control
function is not affected.