9-23
IM 05P02D41-01EN
Program Pattern Functions
9
9.7
Setting Event Functions
The event functions allow outputting an alarm at a preset time under the process of
program operation, or turning on the contact output after a specified time elapses. There
are two types of event action. One is PV event and the other is time event.
Two types of event action, PV event and time event, can be registered with the program
operation, and one type of event action, local event, can be registered with the local
operation.
Up to 2 PV events and up to 4 time events can be set for one program pattern, and up to
2 local events can be set for local operation.
The event action for program operation starts at the time when the segment for which the
event action is set starts.