9-17
IM 05P02D41-01EN
Program Pattern Functions
9
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
JC
Junction code
STD
CONT: Switching for continuation
HOLD: Hold-on switching (the
controller holds the end-of-
segment setpoint when the
segment is completed, to perform
control).
LOC: Local-mode switching (the
controller switches to a local
setpoint when the segment is
completed).
W.SW: Wait during switching between
segments.
W.IV: Wait within a segment interval.
W.SL: Segment switching (the
controller switches to a local
setpoint when the segment is
completed after release.)
PLK.1 to PLK.2 (PLK.4 when the
option
“/AP” is specified.)
: Linked
to patterns 1 to 2 (4.)
INS.: Allows a segment to be added
to the end of a specified segment.
DEL.: Allows a specified segment to
be deleted.
PROG
WT.SW1
Wait function
ON/OFF
STD
OFF: Disable
ON: Enable
WT.UP1
Upper-side wait
zone
STD
0.0 to 10.0% of PV input range (EU)
WT.LO1
Lower-side wait
zone
STD
WT.TM1
Wait time
STD
OFF: No function
0.00 to 999.59 (“hour.minute” or
“minute.second”)
* Available only for the wait time at
the segment switching.
* Use the parameter TMU to set
the time unit. (Common in the
instrument.)
TMU
Program time
unit
EASY
HH.MM: hour.minute
MM.SS: minute.second
CTL
The table below shows which JC parameter settings correspond to which set of the wait
zone parameter
(WZ.UP1, WZ.LO1) and wait time parameter (WT.TM1.)
Setting value of JC
W.SW
WT.TM1
WZ.UP1
WZ.LO1
Setting value of JC
W.IV
WZ.UP1
WZ.LO1
9.4 Setting the Wait Functions