9-19
IM 05P02D41-01EN
Program Pattern Functions
9
9.5
Setting the Segment Repetition
Description
Repeat functions enable you to repeat successive segments in a program pattern a
multiple number of times.
To use the repeat operation, set the repeat cycle start segment number, repeat cycle end
segment number and number of repeat cycles.
One set of repeat operation can be set for each program pattern.
2
3
4
5
6
3
4
5
6
7
8
Segment 1
Repetition zone
Repeat cycle start segment
number (R.STRT) = 3
Repeat cycle end segment
number (R.END) = 6
Number of repeat cycles = 1
When the ramp-prioritized PV start is selected, the start code (STC) setting for the repeat
cycle start segment becomes enabled.
When STC is set to SSP start (STC =
SSP start), repeat operation starts from
the final target setpoint (TSP) for segment
5. When the time-prioritized PV start or
ramp-prioritized PV start is selected,
repeat operation starts from PV.
Time
Setpoint
When time-prioritized PV start or ramp-prioritized PV start is set in the start code (STC),
the start code (STC) setting applies to the repeat operation start.
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
R.CYCL
Number of repeat
cycles
STD
0 to 999, CONT (The controller
indefinitely repeats the segment
specified by the R.STRT and
R.END parameters.)
PROG
R.STRT
Repeat cycle start
segment number
STD
1 to 20 (40 when the option “/AP”
is specified.)
1 ≤ R.STRT ≤ R.END ≤ 20 (40)
R.END
Repeat cycle end
segment number
STD