17-9
IM 05P02D41-01EN
Installation and W
iring
17
Relay Output
(For Standard model) Standard type output
(For Detailed model) Suffix code of Output 1 =
“-R” or “-U”
(For Standard model) Heating/cooling type
heating/cooling output
(For Detailed model) Suffix code of Output 1 = “-R”
or “-U” and Suffix code of Output 2 = “R” or “U”
NC
NO
COM
101
102
103
OUT
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
NO2
NO1
COM
101
102
103
OUT/OUT2
Cooling-side
Heating-side
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
Suffix code: Output 1 and Output 2 = “-UU”, “-UR”,
“-RU” or “-RR”
Terminal 102 has no function in “-AU” and “-AR.”
Note: The control output should always be used with a load of 10 mA or more.
Triac Output (for Detailed model)
(For Detailed model) Suffix code of Output 1 = “-T”
OUT
NO
COM
101
102
103
Contact rating: 75-250 V AC
Allowable load current: 0.8 A
Current and Voltage Pulse Output
(For Standard model) Standard type or
Heating/cooling type heating-side output
(For Detailed model) Suffix code of Output 1 =
“-A” or “-U”
(For Standard model) Heating/cooling type
cooling-side output
(For Detailed model) Suffix code of Output 2 =
“A” or “U”
208
207
OUT
Shield
–
+
Control valves
(or other
actuators)
Current:
4 to 20 mA DC or 0 to 20 mA DC
(resistance load: 600
Ω
or less)
Voltage pulse:
On-voltage: 12 V DC or more
(load resistance: 600
Ω
or more)
Off-voltage: 0.1 V DC or less
Grounding
512
511
RET/OUT2
Shield
–
+
Current:
4 to 20 mA DC or 0 to 20 mA DC
(resistance load: 600
Ω
or less)
Voltage pulse:
On-voltage: 12 V DC or more
(load resistance: 600
Ω
or more)
Off-voltage: 0.1 V DC or less
Grounding
Control valves
(or other
actuators)
Use
When current/voltage pulse output is not used for control output, it can be used for
retransmission output.
When retransmission output terminal is not used for retransmission output, it can be used
for optional control output. The current output range can be changed.
For control output setting, set the control type (CNT), then set the output terminal and
output type in the output type selection (OT).
► Control output type: 10.1 Setting Control Output Type
17.4 Wiring