13-7
IM 05P02D41-01EN
Display
, Key
, and Security Functions
13.1.5 Registering SELECT Parameter Display (Up to 10 Displays)
Description
Registering frequently changed operation parameters (change frequency is lower than
SELECT Display) in the SELECT Parameter Display will allow you to change parameter
settings easily. A maximum of ten Displays can be registered.
Set the D register number of the parameter you wish to register for the registration to the
SELECT Parameter Display.
However, the parameters in the following menus cannot be set:
CTL, PV, MPV, OUT, HBA, R485, ETHR, PROF, DNET, CC-L, KEY, DISP, CSEL, KLOC,
MLOC, DI.SL, DI.NU, DI.D, ALM, DO, I/O, SYS, INIT, VER, and LVL.
When each parameter is displayed, the terminal area (E1 to E4) is displayed on Group
display according to the suffix code and optional suffix code.
MODE Menu Display
Registered
SELECT Parameter Display
Parameter Setting Displays
CS Menu Display
• • • •
• • • •
• • • •
Ordinary Operation Display
CS Menu is not displayed if
SELECT parameter is not
registered.
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
CS10 to
CS19
SELECT parameter-10
to -19 registration
PRO
OFF: No registration
D register number (2201 to
5000)
CSEL
For D register numbers, see the UTAdvanced Series Communication Interface User’s Manual.
13
13.1 Setting Display Functions