8-17
IM 05P02D41-01EN
Control Functions
8.2.4 PD Control (Stable Control in Which a Setpoint is not Exceeded)
Description
This control type performs control in which integral action (I action) is excluded from PID
action.
Set the integral time (I or Ic) to OFF.
It is useful when stable control in which a setpoint is not exceeded is desired for integral
processes in which constant flows are delivered.
The following shows the PID control computation formula.
MR
∆
PV
d
e
P
OUT
+
+
=
•
dt
100
Td
where OUT: control output, e: deviation (PV-SP), P: proportional band, Td: derivative time,
∆PV: PVn-PVn-1 (n-1: value before one control period), and MR: manual reset
The following table shows combination of PD control and output method.
Output method
Current
output
Time
proportional
output
ON/OFF
output
Position
proportional
output
PD control
√
√
N/A
√
√: Available, N/A: Not available
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
P
Proportional band
EASY
0.0 to 999.9%
When 0.0% is set, it operates as 0.1%.
PID
D
Derivative time
EASY
OFF: Disable
1 to 6000 s
MR
Manual reset
EASY
-5.0 to 105.0%
Note1: The PID number (1 to 4, or R) is displayed on Group display while the parameter P,
D, or MR is displayed.
8
8.2 Setting Control Type (CNT)
Summary of Contents for UP35A
Page 3: ......
Page 15: ...Blank Page...
Page 35: ...Blank Page...
Page 37: ...Blank Page...
Page 47: ...Blank Page...
Page 229: ...Blank Page...
Page 251: ...Blank Page...
Page 317: ...Blank Page...
Page 387: ...Blank Page...
Page 409: ...Blank Page...
Page 411: ...Blank Page...