5-5
IM 05P02D41-01EN
Quick Setting Function
5
5.1 Setting Using Quick Setting Function
Input Function (Continued)
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
SDP
PV input scale
decimal point
position
EASY
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
PV
SH
Maximum value of
PV input scale
EASY
-19999 to 30000, (SL<SH),
| SH - SL | ≤ 30000
SL
Minimum value of
PV input scale
EASY
► Input setting: 7.1 Setting Functions of PV Input
Output Function
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
OT
Output type selection
EASY
Control output or Heating-side
control output (Lower two digits)
00: OFF
01: OUT terminals (voltage pulse)
02: OUT terminals (current)
03: OUT terminals (relay/triac)
06: OUT2 terminals (relay)
07: RET/OUT2 terminals (voltage
pulse)
08: RET/OUT2 terminals (current)
Cooling-side control output (Upper
two digits)
00: OFF
01: OUT terminals (voltage pulse)
02: OUT terminals (current)
03: OUT terminals (relay/triac)
06: OUT2 terminals (relay)
07: RET/OUT2 terminals (voltage
pulse)
08: RET/OUT2 terminals (current)
OUT
CT
Control output cycle
time
Heating-side control
output cycle time
(in Heating/cooling
control)
EASY
0.5 to 1000.0 s
CTc
Cooling-side control
output cycle time
EASY
► Output type: 10.1 Setting Control Output Type
► Cycle time: 10.2 Setting Control Output Cycle Time