9-22
IM 05P02D41-01EN
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
JC
Junction code
STD
CONT: Switching for continuation
HOLD: Hold-on switching (the
controller holds the end-of-
segment setpoint when the
segment is completed, to
perform control).
LOC: Local-mode switching (the
controller switches to a local
setpoint when the segment is
completed).
W.SW: Wait during switching
between segments.
W.IV: Wait within a segment
interval.
W.SL: Segment switching (the
controller switches to a local
setpoint when the segment is
completed after release.)
PLK.1 to PLK.2 (PLK.4 when
the option “/AP” is specified.):
Linked to patterns 1 to 2 (4.)
INS.: Allows a segment to be
added to the end of a specified
segment.
DEL.: Allows a specified segment
to be deleted.
PROG
9.6 Operation with Linked Program Patterns