12-4
IM 05P02D41-01EN
Bit-0 to Bit-2 of Program Pattern Number (PT.B0 to PT.B2)
The program pattern number can be switched using contact input. There are three
methods to specify program pattern number.
• Status switch 1 (Operation by keystroke or via communication is enabled depending
on the conditions.)
Program pattern
number
Contact status
PT.B2
PT.B1
PT.B0
1
OFF
OFF
ON
2
OFF
ON
OFF
3
OFF
ON
ON
4
ON
OFF
OFF
*1: “1” when the contact input is turned on and “0” when turned off.
*2: Program pattern number can be switched by keystroke or via communication when all contact
inputs of PT.B0 to PT.B2 are turned off.
*3: Program pattern number cannot be switched by keystroke or via communication when any
contact input of PT.B0 to PT.B2 is turned on.
*4: The contact input is turned off when the bit of program pattern number is not assigned to the
contact input.
*5: The immediately preceding program pattern number is held when all contact inputs are turned
off.
• Status switch 2 (Operation by keystroke or via communication is disabled.)
Program pattern
number
Contact status
PT.B2
PT.B1
PT.B0
1
OFF
OFF
OFF
2
OFF
OFF
ON
3
OFF
ON
OFF
4
OFF
ON
ON
*1: “1” when the contact input is turned on and “0” when turned off.
*2: Contact input is turned off when the bit of program pattern number is not assigned to the contact
input.
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
PT.BC
Bit changing method
of program pattern
number
PRO
0: Status switch 1
1: Status switch 2
DI.NU
12.1 Setting Contact Input Function
Summary of Contents for UP35A
Page 3: ......
Page 15: ...Blank Page...
Page 35: ...Blank Page...
Page 37: ...Blank Page...
Page 47: ...Blank Page...
Page 229: ...Blank Page...
Page 251: ...Blank Page...
Page 317: ...Blank Page...
Page 387: ...Blank Page...
Page 409: ...Blank Page...
Page 411: ...Blank Page...