18-25
IM 05P02D41-01EN
Parameters
18
Heater Break Alarm Setting Menu (Menu: HBA)
Parameter
symbol
Name
Display
level
Setting range
Initial value
HB1.S,
HB2.S
Heater break
alarm-1, -2 function
selection
EASY
0: Heater current measurement
1: Heater break alarm
1
HB1, HB2
Heater break
alarm-1, -2 current
setpoint
EASY
OFF, 0.1 to 300.0 Arms
OFF
CT1.T, CT2.T
CT1, CT2 coil
winding number
ratio
EASY
1 to 3300
800
HDN1, HDN2
Heater break
alarm-1, -2 On-
delay timer
STD
0.00 to 99.59 (minute.second)
0.00
HDF1, HDF2
Heater break
alarm-1, -2 Off-
delay timer
PRO
0.00
HB1.D,
HB2.D
Heater break
alarm-1, -2 contact
type
PRO
CLS: When the event occurs, the
contact is closed.
OPN: When the event occurs, the
contact is opened.
CLS
RS-485 Communication Setting Menu (Menu: R485) (UP35A: E3 terminal area,
UP32A: E1 terminal area)
Parameter
symbol
Name
Display
level
Setting range
Initial value
PSL
Protocol selection
EASY
PCL: PC link communication
PCLSM: PC link communication
(with checksum)
LADR: Ladder communication
CO-M: Coordinated master station
MBASC: Modbus (ASCII)
MBRTU: Modbus (RTU)
P-P: Peer-to-peer communication
MBRTU
BPS
Baud rate
EASY
600: 600 bps
1200: 1200 bps
2400: 2400 bps
4800: 4800 bps
9600: 9600 bps
19200: 19.2k bps
38400: 38.4k bps
19200
PRI
Parity
EASY
NONE: None
EVEN: Even
ODD: Odd
EVEN
STP
Stop bit
EASY
1: 1 bit, 2: 2 bits
1
DLN
Data length
EASY
7: 7 bits, 8: 8 bits
8
ADR
Address
EASY
1 to 99
1
RP.T
Minimum response
time
PRO
0 to 10 (x10ms)
0
When each parameter is displayed, the terminal area (E3) is displayed on Group display.
• Parameter: PSL, BPS, STP, DLN, ADR, RP.T
18.2 List of Parameters