Control Computation Function
Control Specifications
(1) Control Mode
Single-loop control.
(2) Control period
200 ms
Model and
suffix code
(See the
model code)
Number
of analog
input
points
Number
of analog
output
points
(*1)
Number
of contact
input
points
Number of
contact
output
points
(*2)
UP35A
-x0x
1
1
3
3
-x1x
1
1
8
8
UP32A
-x0x
1
1
3
3
-x2x
1
1
5
5
*1: Excluding control output
*2:
Excluding control output relays
Control Computation Specifications
(1) Combination of types of control and control
modes
• PID control
• ON/OFF control
• Heating and cooling control
(2) Control Computation Function
(a) The number of PID parameter groups
Four sets of PID parameters can be set.
(b) Selecting the PID parameter group
The following PID parameter groups can be selected.
• Segment PID
• Measured input zone PID
• Target setpoint zone PID
• Reached target setpoint zone PID
• Local PID
• Reference deviation
(c) Auto-tuning
• Tuning results can be selected from two options,
Normal or Stable.
• Tuning output limit can be set. (It cannot be used in
heating/cooling control.)
(d) “Super” function: Overshoot-suppressing function
(e) “Super 2” function: Hunting-suppressing function
(f) RESET preset output function
(g) Input ERROR preset output function
(h) MANUAL preset output function
(3) Operation Mode Switching
Operation
mode
switching
Start of program operation (PROG)
Stop of program operation (RESET)
Start of local-mode operation (LOCAL)
Start of remote-mode operation (REM)
Pause/cancel release of program operation (HOLD)
Advance of segment (ADV)
Automatic (AUTO)/Manual (MAN) switching
(4) Control Parameter Setting Range
Proportional band
0.1 to 999.9%
Integral time
1 to 6000 sec. or OFF (using manual
reset)
Derivative time
1 to 6000 sec. or OFF
ON/OFF control hysteresis
(one
or two hysteresis points)
0.0 to 100.0% of measured input
range width
Preset output value
-5.0 to 105.0% (however, 0 mA or less
cannot be output)
High/low output limiter
-5.0 to 105.0%
Low limit setpoint < high limit setpoint
Tight shut function
When manual control is carried out
with 4 to 20 mA output, control output
can be reduced to about 0 mA.
Rate-of-change limiter of
output
0.1 to 100.0%/sec., OFF
Output dead band
For heating and cooling control:
-100.0 to 50.0%
For position proportional control: 1.0
to 10.0%
Alarm Functions
• Types of Alarm
Measured value
alarm
Deviation alarm
Rate-of-change
alarm
PV (measured value) high/low limit alarm
Deviation high/low limit alarm
Deviation high and low limits alarm
Deviation within high and low limits alarm
Analog input PV high/low limit alarm
Auxiliary analog input high/low limit alarm
Feedback input high/low limit alarm
PV rate-of-change alarm
Setpoint alarm
SP (setpoint) high/low limit alarm
Target SP high/low limit alarm
Target SP deviation high/low limit alarm
Target SP deviation high and low limits alarm
Target SP deviation within high and low limits alarm
Output alarm
Control output high/low limit alarm
Cooling control output high/low limit alarm
Other alarms
Heater disconnection alarm (for /HA option)
Self-diagnosis alarm
FAIL
• Alarm Functions
Alarm output action
Alarm stand-by action
Alarm latch (forced reset) function
Alarm hysteresis
Alarm ON/OFF delay timer
Number of alarm settings
2
Number of alarm output points
Max. 2
Contact I/O Function
This function allows for allocating the input error
condition, operation condition, alarm condition or other
conditions to the contact input and contact output.
Contact
input
Switch to PROG (Start of program operation)
Switch to RESET (Stop of program operation)
Program pattern 1 to 4 selection and starting the
program operation simultaneously
Switch to LOCAL(LSP) (Start of local-mode operation)
PROG/RESET Switch
PROG/LOCAL(LSP) Switch
PROG/HOLD Switch
Switch to HOLD (Start of hold-mode operation)
Advance of segment
Wait ON/OFF switch
AUTO/MAN switch
Auto-tuning START/STOP switch
Latch release
LCD backlight ON/OFF switch
PV red/white switch
Message interrupt displays 1 through 4
Program pattern number selection
PID number selection
Manual preset output number selection
Contact
output
PV event, Time event, Alarm
Status output