13
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation
GS 05P02D41-01EN Mar.14,2016-00
Terminal Arrangement for UP32A Single Loop Control
E1-terminal area
111
301
302
303
304
305
306
307
308
309
310
311
312
201
202
203
204
205
206
207
208
209
210
101
102
103
104
105
106
107
108
109
110
211
212
101
-112
301
-312
201
-212
112
(Suffix code: Type 1=-2)
ALM
(Equipped
as standard)
Contact output
External contact output (relay)
AL3
AL2
AL1
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
PV event-2 output
Time event-1 output
PV event-1 output
Common
Common
Common
UP
104
105
106
107
108
109
PV
PV input
TC input
RTD input
Voltage (mV, V) input
A
+
-
+
-
Current (mA) input
+
-
B
b
(Equipped
as standard)
202
203
201
202
203
202
203
203
204
Factory default: PV input
type is undefined.
OUT
(Suffix code: Type1=-0)
Control output
101
102
Relay contact output
103
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
Terminal wiring differs in Heating/cooling
control and Position proportional control.
Refer to the terminals of Position
proportional control output and
Heating/cooling control output below.
Factory default: Control output is relay.
OUT
Current/voltage pulse output
0-20 mA DC,
4-20 mA DC,
Voltage pulse (12 V)
+
Retransmission output
+
-
Default: 4-20 mA DC
Default: Undefined
0-20 mA DC,
4-20 mA DC
Control output
(Suffix code: Type1=-0, -1 or -2)
15 V DC loop power supply
14.5-18.0 V DC
(Max. 21 mA DC)
+
-
207
208
207
-
208
207
208
Can be used for retransmission output or 15 V DC loop power supply when
current/voltage pulse output is not used for control output.
Current output range can be changed.
In Position proportional type, can be used for retransmission output or 15 V
DC loop power supply.
RET
Retransmission output
4-20 mA DC or
0-20 mA DC
15 V DC loop power supply
14.5-18.0 V DC
(Max. 21 mA DC)
+
-
+
-
Default: 4-20 mA DC
Default: PV
retransmission
Load resistance 600
Ω
or less
Retransmission output
(Equipped as standard)
205
206
205
206
Can be used for 15 V DC loop
power supply when not used for
retransmission output.
VALV
(Suffix code: Type1=-1)
Position proportional control output
Resistance: 100
Ω
to 2.5 k
Ω
Feedback input
100%
0%
Relay contact output
HIGH
(direct)
LOW
(reverse)
COM
Contact rating: 250 V AC, 3A
30 V DC, 3 A
(resistance load)
101
102
103
310
311
312
-
Feedback input
Current (mA)
input
When feedback input is current
310
311
312
+
HBA
(Option code /HA)
Heater break alarm
Heater current detection input
CT1
CT2
COM
External contact output (transistor)
Transistor contact rating: 24 V DC, 50 mA
Heater break alarm-1
output
Heater break alarm-2
output
Common
310
311
312
HAL1
HAL2
COM
UP
307
308
309
(24 V AC/DC power supply: Option code /DC)
Power supply
100-240 V AC power supply
N
L
Allowable range:
100-240 V AC (+10%/-15%)
(free voltage)
50/60 Hz shared
110
111
24 V AC/DC power supply
-
+
110
111
112
112
N
L
(Suffix code: Type 1=-2)
Cooling-side control output
RET/OUT2
Current/voltage pulse output
0-20 mA DC,
4-20 mA DC,
Voltage pulse (12V)
+
-
205
206
Can not be used for retransmission output or
15 V DC loop power supply when
current/voltage pulse output is used.
Can be used for retransmission output or 15 V
DC loop power supply when control output is
not used.
Current output range can be changed.
Heating/cooling control output
Heating/cooling relay contact output
NO
Heating
-side
Cooling
-side
NO
COM
Contact rating: 240 V AC, 3 A
30 V DC, 3 A (resistance load)
101
102
103
OUT
OUT2
DI
(Equipped as standard)
Contact input
Contact rating: 12 V DC, 10 mA or more
External contact input
DI3
DI2
DI1
COM
Common
DI3
DI2
DI1
COM
+5V
+5V
+5V
No-voltage
contact
Transistor contact
UP
UP
209
210
211
212
209
210
211
212
Function can be changed.
Start of program operation when
DI1 changes from OFF to ON.
Stop of program operation when
DI2 changes from OFF to ON.
Start of local-mode operation when
DI3 changes from OFF to ON.
E1端子エリア
301-312
RS-485
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
RS-485 communication
(Suffix code:
Type 2=1)
301
302
303
304
305
RS485
(Suffix code: Type 2=2)
External contact output
Transistor contact rating: 24 V DC, 50 mA
DO12
DO11
COM
Common
UT
Contact input / Contact output
External contact input
DI11
DI12
COM
Common
DI11
DI12
COM
+5V
+5V
No-voltage
contact
Transistor
contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
UT
UT
301
302
303
301
302
303
304
305
306
DI/DO
Function can be
assigned to the
terminals with no
function.
CC-Link communication (with Modbus master)
(Suffix code: Type 3=3)
FG: Flame ground
SLD: Shield
DG: TX/RX signal ground
DB: RX/TX signal - signal
DA: RX/TX signal
CHK(red)
(Lit: User profile error/Adress error, Unlit: Normal
)
L ERR(red)
(Lit: Communication failure(CRC error), Unlit: Normal
)
L RUN(green)
(Lit: Normal, Unlit: No carrier detected/Communication timeout)
Not used
301
302
303
304
305
306
307
308
309
RS-485
RSB(+)
RSA(-)
SG
310
311
312
DB
DA
110Ω
CC-L
If the UT is located at the end of a
segment for the CC-Link
communication wiring,terminating
resistors are separately needed.
These are to be prepared by
users. (110 Ω: 1 pc.)
Summary of Contents for UP35A
Page 3: ......
Page 15: ...Blank Page...
Page 35: ...Blank Page...
Page 37: ...Blank Page...
Page 47: ...Blank Page...
Page 229: ...Blank Page...
Page 251: ...Blank Page...
Page 317: ...Blank Page...
Page 387: ...Blank Page...
Page 409: ...Blank Page...
Page 411: ...Blank Page...