6-16
IM 05P02D41-01EN
6.3 Adjusting PID Manually
Setting Display
Parameter Setting Display
Operation Display >
PARAMETER
key or
PARA
key for
3
seconds
(to [
MODE
] Menu Display) >
Right arrow
key (to [
PID
]
Menu Display ) >
SET/ENTER
key (The setting parameter
is displayed.) >
Down arrow
key (The setting parameter is
displayed.)
In the Setting Display for the PID parameters, Displays can
be arbitrarily switched using the Up, Down, Left or Right arrow
key. Pressing the Left or Right arrow key changes the group.
(The group number is displayed on Group display.)
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
P
Proportional band
Heating-side
proportional band
(in Heating/cooling
control)
EASY
0.0 to 999.9%
When 0.0% is set, it operates as
0.1%.
Heating-side ON/OFF control
applies when 0.0% in Heating/
cooling control
PID
I
Integral time
Heating-side
integral time (in
Heating/cooling
control)
EASY
OFF: Disable
1 to 6000 s
D
Derivative time
Heating-side
derivative time (in
Heating/cooling
control)
EASY
OFF: Disable
1 to 6000 s
Pc
Cooling-side
proportional band
EASY
0.0 to 999.9%
Cooling-side ON/OFF control
applies when 0.0% in Heating/
cooling control
Ic
Cooling-side
integral time
EASY
OFF: Disable
1 to 6000 s
Dc
Cooling-side
derivative time
EASY
OFF: Disable
1 to 6000 s
There are four groups of PID parameters.
The PID parameters can be selected by using the following two methods:
(1) Segment PID number selection
(2) Zone PID selection
(3) Local PID selection
►
Selection by contact input: 12.1 Setting Contact Input Function
►
Selection by each Zone: 8.4 Switching PID