9
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation
GS 05P02D41-01EN Mar.14,2016-00
Transportation and Storage Conditions:
• Temperature: -25 to 70ºC
• Temperature change rate: 20ºC/h or less
• Humidity: 5 to 95% RH (no condensation allowed)
Effects of Operating Conditions
• Effect of ambient temperature:
Voltage or TC input: ±1 µV/ºC or ±0.01% of F.S./ºC,
whichever is larger
Current input: ±0.01% of F.S./ºC
RTD input: ±0.05ºC/ºC (ambient temperature) or less
Analog output: ±0.02% of F.S./ºC or less
• Effect of power supply voltage fluctuation
Analog input: ±0.05% of F.S. or less
Analog output: ±0.05% of F.S. or less
(Each within rated voltage range)