11-9
IM 05P02D41-01EN
Alarm Functions
11
Fault diagnosis Alarm
The function outputs an alarm signal in the following cases.
The corresponding event (EV) lamp is lit and the contact output turns on (when the
contact type is energized).
• Burnout of PV input
• ADC failure of PV input
• Reference junction compensation (RJC) error
of PV input
The fault diagnosis alarm does not work the stand-by action functions.
FAIL output
When the FAIL condition is caused (faulty MCU or system data error), DO (alarm output)
turned off regardless of contact type.
The FAIL output does not work the alarm latch, the energized/de-energized and the
stand-by action functions.
Stand-by Action
The stand-by action is a function for ignoring the alarm condition and keeps the alarm off
until the alarm condition is removed. Once the alarm condition is removed, the stand-by
action is cancelled.
It is effective in the following cases where;
• The power is turned on
• The alarm type is changed
• Forced stand-by via communication
The following shows the behavior of an alarm with the stand-by action at power ON.
Treated
as normal
ºC
Power-on
Time
The alarm output does not turn on
in this region even if the PV valule
is below PV low limit alarm setpoint.
PV low limit alarm setpoint
Normal
Abnormal
The alarm output
turns on.
11.1 Setting Alarm Type