13-6
IM 05P02D41-01EN
13.1.4 Changing Event Display
Description
The UP35A has eight event (EV) lamps.
PV events are assigned to EV1 to EV2 lamps on the front of the controller.
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu
symbol
EV1 to
EV2
EV1 to EV2
display
condition
registration
PRO
Setting range: 4001 to 6304
OFF: Disable
4785: Link to PV event 1 (Lit when the PV
event-1 occurs)
4786: Link to PV event 2 (Lit when the PV
event-2 occurs)
4529: Heater break alarm 1 (Lit when the alarm
occurs)
4530: Heater break alarm 2 (Lit when the alarm
occurs)
5025 to 5027: Link to DI1-DI3 (Lit when the
contact is closed)
5089 to 5093: Link to DI41-DI45 (E4-terminal
area) (Lit when the contact is closed)
5153 to 5155: Link to AL1-AL3 (Lit when the
contact is closed)
5169 to 5173: Link to DO11-DO15 (E1-terminal
area) (Lit when the contact is closed)
5217 to 5221: Link to DO41-DO45 (E4-terminal
area) (Lit when the contact is closed)
For other functions, see the UTAdvanced
Series Communication Interface User’s
Manual.