6-30
IM 05P02D41-01EN
The hold operation function allows pausing the progress of the program pattern.
The hold operation stops the segment time and the time of the time event. As a result,
the segment time and the time of the time event are extended by the amount of the
holding time.
Releasing the hold state restarts the segment time and the time of the time event from
the time when they were stopped. When the hold state is released, the action can be
checked in the Deviation indicator (Program monitor display) on the front panel.
Control during the hold operation is performed using the setpoint at the time when the
hold operation starts. The time event keeps the state and the PV event continues the
action at the time when the hold operation starts.
►
6.9 Changing SP, TSP, or Remaining Segment-time (R.TIM) in HOLD-mode
Hold Operation in Soak Segment
Seg.2
Seg.1
Seg.3
Seg.4
Seg.5
Seg.6
Seg
:
Segment
Setpoint
Time
Hold interval
(
Timer stops
)
Hold interval
(
Timer stops
)
Time event
On
Off
Time delayed by timer stops
Time delayed by timer stops
Program pattern before
excuting hold operation.
Hold Operation in Ramp Segment
Seg.1
Seg.1
Seg.3
Seg.2
Seg.2
Seg.3
Seg.4
Seg.4
Seg.5
Seg.5
Seg.6
Seg.6
Seg
:
Segment
Setpoint
Time
Hold interval
(
Timer stops
)
Hold interval
Time event
On
Off
Time delayed by timer stops
Program pattern before
excuting hold operation.
Program pattern after
excuting hold operation.
6.6 Switching Operation Modes
Summary of Contents for UP35A
Page 3: ......
Page 15: ...Blank Page...
Page 35: ...Blank Page...
Page 37: ...Blank Page...
Page 47: ...Blank Page...
Page 229: ...Blank Page...
Page 251: ...Blank Page...
Page 317: ...Blank Page...
Page 387: ...Blank Page...
Page 409: ...Blank Page...
Page 411: ...Blank Page...