8-20
IM 05P02D41-01EN
8.4 Switching PID
8.4.1 Switching PID According to Target Setpoint Number (SPNO)
Description
The segment PID selection selects a group of PID parameters according to switching
segment of the program pattern.
The segment PID number selection (S.PID) can be set for each segment.
For the operation except the program pattern operation, the PID parameter is selected by
the PID number which is specified in the parameter L.PID (Local PID number selection).
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
ZON
Zone PID
selection
STD
0: Segment PID selection
1: Zone PID selection (selection
by PV)
2: Zone PID selection (selection
by target SP)
4: Zone PID selection (selection
by SP)
5: Local PID selection
CTL
S.PID
Segment PID
number selection
EASY
1 to 4
PROG
L.PID
Local PID
number selection
EASY
1 to 4
LOC
PID
PID number
(display only)
EASY
1 to 4
MODE
Note 1: A currently-used PID number is displayed for the parameter PID.