Communications D - 12
002BH
Sequence input status
Bit 0
Input terminal S1 1: ON 0: OFF
Bit 1
Input terminal S2 1: ON 0: OFF
Bit 2
Multi-function digital input terminal S3 1: ON 0: OFF
Bit 3
Multi-function digital input terminal S4 1: ON 0: OFF
Bit 4
Multi-function digital input terminal S5 1: ON 0: OFF
Bit 5
Multi-function digital input terminal S6 1: ON 0: OFF
Bit 6
Multi-function digital input terminal S7 1: ON 0: OFF
Bits 7 to F
Not used
002CH
Drive status
Bit 0
Operation
1: Operating
Bit 1
Zero speed
1: Zero speed
Bit 2
Frequency agree
1: Matched
Bit 3
Desired frequency agree
1: Matched
Bit 4
Frequency detection 1
1: Output frequency
≤
L4-01
Bit 5
Frequency detection 2
1: Output frequency
≥
L4-01
Bit 6
Drive startup completed
1: Startup completed
Bit 7
Low voltage detection 1: Detected
Bit 8
Baseblock
1: Drive output baseblock
Bit 9
Frequency reference mode
1: Not communication 0: Communication
Bit A
Run command mode
1: Not communication 0: Communication
Bit B
Overtorque detection
1: Detected
Bit C
Frequency reference lost
1: Lost
Bit D
Retrying error
1: Retrying
Bit E
Error (including Modbus communications time-out) 1:Error occurred
Bit F
Modbus communications time-out 1: Timed out
002DH
Multi-function digital output status
Bit 0
Multi-function digital output 1 (terminal M1-M2) 1: ON 0: OFF
Bit 1
Multi-function digital output 2 (terminal M3-M4): 1: ON 0: OFF
Bit 2
Not used
Bits 3 to F
Not used
002EH - 0030H
Not used
0031H
Main circuit DC voltage
0032H - 0037H
Not used
0038H
PI feedback level (Input equivalent to 100%/Max. output frequency; 10/1%; without sign)
0039H
PI input level (±100%/±Max. output frequency; 10/1%; with sign)
003AH
PI output level (±100%/±Max. output frequency; 10/1%; with sign)
003BH
CPU software number
003CH
Flash software number
003DH
Communication error details
Bit 0
CRC error
Bit 1
Invalid data length
Bit 2
Not used
Bit 3
Parity error
Bit 4
Overrun error
Bit 5
Framing error
Bit 6
Time-out
Bits 7 to F
Not used
003EH
KVA setting
003FH
Control method
Note: Communication error details are stored until an error reset is input (errors can be reset while the Drive is operating).
Table D.5 Monitor Data (Continued)
Register No.
Contents
Summary of Contents for E7LBA002
Page 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Page 8: ...Introduction vi Notes ...
Page 12: ...Table of Contents x Notes ...
Page 54: ...Electrical Installation 2 22 Wiring Diagram ...
Page 55: ...Electrical Installation 2 23 ...
Page 87: ...Start Up and Operation 4 9 Notes ...
Page 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Page 248: ...Capacity Related Parameters B 6 Notes ...
Page 279: ...Communications D 27 Note ...
Page 280: ...Communications D 28 ...
Page 292: ...Spare Parts F 6 ...
Page 304: ...Index 12 ...
Page 305: ......