Parameters A - 6
b5-08
PI Primary Delay Time
Constant
PI Delay Time
Sets the amount of time for a filter on the output of the PI
controller.
0.00 to
10.00
0.00sec
Programming
b5-09
PI Output Level Selection
Output Level Sel
Determines whether the PI controller will be direct or reverse
acting.
0: Normal Output (direct acting)
1: Reverse Output (reverse acting)
0 or 1
0
Programming
Denotes that parameter can be changed when the drive is running.
b5-10
PI Output Gain Setting
Output Gain
Sets the output gain of the PI controller.
0.0 to 25.0
1.0
Programming
b5-11
PI Output Reverse Selection
Output Rev Sel
0: 0 limit (when PI output goes negative Drive stops)
1: Reverse (when PI goes negative Drive reverses)
0 limit automatic when reverse prohibit is selected using b1-04
0 or 1
0
Programming
b5-12
PI Feedback Reference
Missing Detection Selection
Fb los Det Sel
0: Disabled
1: Alarm
2: Fault
0 to 2
0
Programming
b5-13
PI Feedback Loss Detection
Level
Fb los Det Lvl
Sets the PI feedback loss detection level as a percentage of
maximum frequency (E1-04).
0 to 100
0%
Programming
b5-14
PI Feedback Loss Detection
Time
Fb los Det Time
Sets the PI feedback loss detection delay time in terms of seconds.
0.0 to 25.5
1.0sec
Programming
b5-15
Sleep Function Start
Level
Sleep Level
Sets the sleep function start frequency.
0.0 to 200.0
0.0Hz
Programming
b5-16
Sleep Delay Time
Sleep Time
Sets the sleep function delay time in terms of seconds.
0.0 to 25.5
0.0sec
Programming
b5-17
PI Accel/Decel Time
Acc/Dec Time
Applies an accel/decel time to the PI setpoint reference.
0.0 to 25.5
0.0sec
Programming
b5-18
PI Setpoint Selection
PI Setpoint Sel
0: Disabled
1: Enabled
0 or 1
0
Programming
b5-19
PI Setpoint Value
PI Setpoint
Depends on b5-20.
0.00 to
100.00**
0.00%
Programming
b5-20
PI Setpoint Display Scaling
Setpoint Scaling
Set display/setting Unit of b5-19, U1-24, and U1-38.
0 to 39999
1
Programming
b5-21
PI Sleep Input Source
PI Sleep Source
Input Source Selection for Sleep function Mode.
0: PI Setpoint
1: SFS Input (This is near the PI output)
2: Snooze
0 to 2
1
Programming
b5-22
PI Snooze Level
Snooze Level
Sets the PI snooze function start level as a percentage of maximum
frequency (E1-04).
0 to 100
0%
Programming
b5-23
PI Snooze Delay Time
Snooze Delay Time
Sets the PI snooze function delay time in terms of seconds.
0 to 3600
0sec
Programming
b5-24
PI Snooze Deactivation Level
Wake-Up Level
When the PI feedback drops below this level, normal PI operation
starts again. Set as a percentage of maximum frequency (E1-04).
0 to 100
0%
Programming
b5-25
PI Setpoint Boost Setting
Setpoint Boost
Temporary increase of PI setpoint to create an overshoot of the
intended PI setpoint.
0 to 100
0%
Programming
b5-26
PI Maximum Boost Time
Max Boost Time
Sets a time limitation for reaching temporarily boosted PI setpoint
(intended PI se b5-25).
0 to 3600
0sec
Programming
b5-27
PI Snooze Feedback Level
Snooze Feedback
PI snooze mode will be activated when PI feedback is above this
level. Set as a percentage of maximum frequency (E1-04).
0 to 100
60%
Programming
Denotes that parameter can be changed when the drive is running. ** Range depends on b5-20 setting. Units depend on b5-31 setting.
Table A.1 Parameter List (Continued)
Parameter
No.
Parameter Name
LCD Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Summary of Contents for E7LBA002
Page 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Page 8: ...Introduction vi Notes ...
Page 12: ...Table of Contents x Notes ...
Page 54: ...Electrical Installation 2 22 Wiring Diagram ...
Page 55: ...Electrical Installation 2 23 ...
Page 87: ...Start Up and Operation 4 9 Notes ...
Page 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Page 248: ...Capacity Related Parameters B 6 Notes ...
Page 279: ...Communications D 27 Note ...
Page 280: ...Communications D 28 ...
Page 292: ...Spare Parts F 6 ...
Page 304: ...Index 12 ...
Page 305: ......