![background image](http://html.mh-extra.com/html/yaskawa/e7lba002/e7lba002_technical-manual_907669189.webp)
Diagnostic & Troubleshooting 6 - 17
Auto-Tuning Faults
Auto-tuning faults are shown below. When the following faults are detected, the fault is displayed on the digital operator and
the motor coasts to a stop during operation. The fault contact is not activated.
Table 6.6 Auto-Tuning Displays and Processing
Digital Operator Display
Probable Cause
Corrective Action
Er - 01
Fault
• There is an error in the data input
for autotuning.
• There is an error in the relationship
between the motor output and the
motor rated current.
• Check input data.
• Check Drive and motor capacity.
• Check motor rated current.
Er - 02
Minor Fault
A minor fault is detected during
auto-tuning.
• Check input data.
• Check wirings and around the
machine.
• Check the load.
Er - 03
STOP key
The STOP key is pressed during
auto-tuning, and the auto-tuning is
interrupted.
–
Er - 04
Resistance
Auto-tuning is not completed within
the specified time.
The auto-tuning result became other
than the parameter set range.
• Check input data.
• Check motor wiring.
• If a motor and a machine are
connected, disconnect the motor
from the machine.
Er - 12
I-det. Circuit
• Current flow exceeded the motor
rated current.
• Current detection value symbol
was reversed.
• Any of U/TI, V/T2, and W/T3 has
open-phase.
• Check current detection circuit,
wiring and mounting procedure.
Er - 13
Leakage Inductance Fault
Auto-tuning did not finish within the
set time.
Tuning result became other than the
parameter setting range.
• Check motor wiring.
End - 3
Data Invalid
Rated current set value is set too
high.
• Check input data (especially,
motor output current and motor
rated current value).
Summary of Contents for E7LBA002
Page 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Page 8: ...Introduction vi Notes ...
Page 12: ...Table of Contents x Notes ...
Page 54: ...Electrical Installation 2 22 Wiring Diagram ...
Page 55: ...Electrical Installation 2 23 ...
Page 87: ...Start Up and Operation 4 9 Notes ...
Page 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Page 248: ...Capacity Related Parameters B 6 Notes ...
Page 279: ...Communications D 27 Note ...
Page 280: ...Communications D 28 ...
Page 292: ...Spare Parts F 6 ...
Page 304: ...Index 12 ...
Page 305: ......