Control Panel 3 - 22
Example of Changing a Parameter
Table 3.19 provides an example of how to change parameter “C1-01” (Acceleration Time 1) from 30 sec to 20 sec.
Table 3.19 Changing a Parameter in the Programming Menu
Step
Number
Digital Operator Display
Description
1
Power supply turned ON.
2
MENU Key pressed to enter drive menu.
3
MENU Key pressed to enter quick programming
menu.
4
MENU Key pressed to enter advanced
programming menu.
5
DATA/ENTER pressed to access monitor display.
6
INCREASE or DECREASE Key pressed to display
C1-01 (Acceleration Time 1).
7
DATA/ENTER Key pressed to access setting
display. The setting of C1-01 (30.00) is displayed.
8
Shift/RESET Key pressed to move the flashing
digit to the right.
9
DECREASE Key pressed to change set value to
20.00 s.
10
DATA/ENTER Key pressed to enter the set data.
“END” is displayed for 10 s and then the entered
value is displayed for 0.5 s.
11
The monitor display for C1-01 returns.