Programming 5 - 8
Options - P "Pneumatic Pressure Transducer"; Bypass with pneumatic input for speed
control:
Hand mode speed command from Keypad/Operator.
Auto mode speed command input signal from the pneumatic transducer, or 4-20 mA applied to Terminal TB5-9
(Drive terminal A2).
Auto mode run/stop contact closure for Drive and Bypass applied to terminals TB1-2 and TB1-9.
Options - J, U, V or L "Serial Communications"; Bypass with serial communication for control:
Hand mode speed command from Keypad/Operator.
Auto mode speed command input signal from serial communication.
Auto mode run/stop command for Drive from serial communication.
Auto mode run/stop command for Bypass from serial communication.
Significant
Parameter Setting
Drive Operational Result
b1-01 = 1: Terminals (default)
Speed command source = Terminals
H3-08 = 2: 4-20 mA (default)
Drive Terminal A2 is programmed for 4-20 mA (Transducer output is 4-20 mA)
(Note – Control PCB DIP switch S1-2 must also be ON)
H3-09 = 0: Frequency Bias
Drive Terminal A2 function is set to “bias” the terminal A1 input. Terminal A1 is
not used, therefore the A2 “bias” signal becomes the speed command.
H1-03 = 3: Multi-Step Ref 1
(default)
A Drive terminal S5 input contact closure selects d1-02 (keypad) as a preset
speed. This input contact is closed when H/O/A = Hand.
Significant
Parameter Setting
Drive Operational Result
b1-01 = 0: Operator
Speed command source = Keypad/Operator (d1-01)
H1-03 = 6C: Com/Inv Sel 2
A Drive terminal S5 input contact closure allows b1-01 to select d1-01 (key-
pad) as a preset speed. An open contact selects serial com for speed command
and run/stop. This input contact is closed when H/O/A = Hand.
H5-02 = Baud Rate
Each protocol requires the baud rate indicated in Table 5.2
H5-07 = RTS Control
Each protocol requires the Request to Send control indicated in Table 5.2
H5-08 = Protocol Selection
Drive communicates via protocol selected. 0: Modbus, 1: N2 or 2: FLN
Summary of Contents for E7LBA002
Page 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Page 8: ...Introduction vi Notes ...
Page 12: ...Table of Contents x Notes ...
Page 54: ...Electrical Installation 2 22 Wiring Diagram ...
Page 55: ...Electrical Installation 2 23 ...
Page 87: ...Start Up and Operation 4 9 Notes ...
Page 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Page 248: ...Capacity Related Parameters B 6 Notes ...
Page 279: ...Communications D 27 Note ...
Page 280: ...Communications D 28 ...
Page 292: ...Spare Parts F 6 ...
Page 304: ...Index 12 ...
Page 305: ......