Electrical Installation 2 - 19
Wiring Checks
After all wiring is completed, perform the following checks:
1.
Is all wiring correct?
2.
Have all wire clippings, screws or other foreign material been removed from the Drive and Bypass enclosure?
3.
Are all terminal screws tight?
Control Circuit Wiring Precautions
Observe the following precautions when wiring control circuits:
1.
Separate control wiring from power/motor wiring and other high-power lines.
2.
Separate wiring for control circuit terminals for digital outputs from wiring to other control circuit terminals.
3.
If using an optional external power supply, it should be a UL Listed Class 2 power supply source.
4.
Use twisted-pair or shielded twisted-pair cables for control circuits to prevent operating faults. Prepare cable ends as
shown in Figure 2.12.
5.
Connect the shield wire to terminal PE.
6.
Insulate the shield with tape to prevent contact with other signal lines and equipment.
Fig 2.12 Preparing the Termination of Shielded Twisted-Pair Cables
Table 2.14 Terminal Numbers and Wire Sizes (Same for all Bypass Units)
Terminals
Terminal
Screws
Tightening
Torque
lb.-in.
(N•m)
Possible
Wire Sizes
AWG
(mm
2
)
Recommended
Wire Size
AWG
(mm
2
)
Wire Type
TB1-1 to 14
TB2-1 to 6
TB3-1 to 4
TB4-1 to 4
TB5-1 to 9
Phoenix
type *
3
4.2 to 5.3
(0.5 to 0.6)
Stranded
wire:
26 to 16
(0.14 to 1.5)
18
(0.75)
• Shielded, twisted-pair wire
*1
• Shielded, polyethylene-covered,
vinyl sheath cable
PE
M3.5
7.0 to 8.8
(0.8 to 1.0)
20 to 14
(0.5 to 2
*2
)
12
(1.25)
*1. Use shielded twisted-pair cables to input an external speed command.
*2. We recommend using straight solderless terminals on digital inputs to simplify wiring and improve reliability.
*3. We recommend using a thin-slot screwdriver with a 3.5 mm blade width.
Shield sheath
Insulation
Connect to shield sheath
terminal PE on PCB A2
Insulate with tape
Do not connect here.
Summary of Contents for E7LBA002
Page 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Page 8: ...Introduction vi Notes ...
Page 12: ...Table of Contents x Notes ...
Page 54: ...Electrical Installation 2 22 Wiring Diagram ...
Page 55: ...Electrical Installation 2 23 ...
Page 87: ...Start Up and Operation 4 9 Notes ...
Page 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Page 248: ...Capacity Related Parameters B 6 Notes ...
Page 279: ...Communications D 27 Note ...
Page 280: ...Communications D 28 ...
Page 292: ...Spare Parts F 6 ...
Page 304: ...Index 12 ...
Page 305: ......