Physical Installation 1 - 5
Bypass Unit Enclosures
All Bypass units are intended for non-hazardous locations. Various enclosure types are provided to protect against the applica-
tion environmental conditions:
Nema Type 1 Enclosures
These are constructed for indoor use to provide a degree of protection against incidental contact with enclosed electrical equip-
ment and falling dust or dirt.
NEMA Type 12 FVFF Enclosures
NEMA provides for both non-ventilated and ventilated NEMA 12 enclosures. When ventilated, a suffix to the type number
defines the ventilation method. A NEMA 12 FVFF enclosure has Forced Ventilation with inlet air Filter and outlet air Filter.
The internal pressure is positive with respect to the ambient pressure. UL does not recognize NEMA 12 ventilated enclosures,
therefore, these enclosures are designated NEMA 1 for UL purposes.
Table 1.4 480V Enclosure Data
Input
Volts
HP
1
Drive
Model
CIMR-
Bypass
2
Model
Number
NEC
FLA
OL
110%
1 min
Heat
3
Loss
Watts
Enclosure Dimensions
4
NEMA 1 & NEMA 12 -FVFF
H W D
inches
Weight
5
of
Assembly
Electrical
Schematic
480
0.5
42P21
E7L_B001
1.1
1.2
57
29.48 19.06 13.66
Dimension Drawing
6
S-5537
115 lbs
E7L-00
0.75
42P21
E7L_B001
1.6
1.8
57
1
42P21
E7L_B002
2.1
2.3
62
2
42P21
E7L_B003
3.4
3.7
89
3
42P21
E7L_B004
4.8
5.3
121
5
43P71
E7L_B007
7.6
8.4
155
7.5
45P51
E7L_B011
11.0
12.1
217
10
47P51
E7L_B014
14.0
15.4
318
127 lbs
15
40091
E7L_B021
21.0
23.1
404
20
40111
E7L_B027
27.0
29.7
408
142 lbs
25
40151
E7L_B034
34.0
37.4
485
30
40181
E7L_B040
40.0
44.0
618
40
40241
E7L_B052
52.0
57.2
1040
40.48 25.63 14.66
Dimension Drawing
6
S-5539
203 lbs
50
40301
E7L_B065
65.0
71.5
1045
232 lbs
60
40371
E7L_B077
77.0
84.7
1197
Note 1: Horsepower rating is based on a standard NEMA B 4-pole motor.
Note 2: The underscore position in these model numbers codes for the enclosure type: V = NEMA1, B = NEMA12 FVFF.
Note 3: Heat loss is the amount of heat dissipated by the drive at full load with all standard options available inside the enclosure. Drive heat sink losses are
included in the heat loss data.
Note 4: Height dimension (H) excludes the mounting screw tabs. Depth dimension (D) excludes the disconnect handle.
Note 5: This data represents the total weight with all possible standard options. Weight could be less depending on the options specified.
Note 6: All standard options are available in this size enclosure.
Summary of Contents for E7LBA002
Page 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Page 8: ...Introduction vi Notes ...
Page 12: ...Table of Contents x Notes ...
Page 54: ...Electrical Installation 2 22 Wiring Diagram ...
Page 55: ...Electrical Installation 2 23 ...
Page 87: ...Start Up and Operation 4 9 Notes ...
Page 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Page 248: ...Capacity Related Parameters B 6 Notes ...
Page 279: ...Communications D 27 Note ...
Page 280: ...Communications D 28 ...
Page 292: ...Spare Parts F 6 ...
Page 304: ...Index 12 ...
Page 305: ......