Parameters A - 24
o1-06
User Monitor Selection Mode
Monitor Mode Sel
Selects the "U1" monitors displayed on the 4th and 5th
lines of the digital operator display.
0: 3 Mon Sequential (Displays the next 2 sequential U1
monitors).
1: 3 Mon Selectable (Displays U1 monitors set by o1-07
and o1-08).
0 or 1
0**
Programming
o1-07
Second Line User Monitor
Selection
2nd Monitor Sel
Sets the "U1" monitor always displayed on the 4th line
of the digital operator display. Effective only when
o1-06 = 1.
1 to 53
2**
Programming
o1-08
Third Line User Monitor
Selection
3rd Monitor Sel
Sets the "U1" monitor always displayed on the 5th line
of the digital operator display. Effective only when
o1-06 = 1.
1 to 53
3**
Programming
o1-09
Frequency Reference Display
Units
Frq Display Unit
Sets unit display for the frequency reference parameters
and frequency related monitors when o1-03
≥
40.
0: WC:InchOfWater
1: PSI:lb/SqrInch
2: GPM:Gallons/Min
3: F:DegFahrenheit
4: CFM:Cubic ft/Min
5: CMH:Cubic M/Hr
6: LPH:Liters/Hr
7: LPS:Liters/Sec
8: Bar:Bar
9: Pa:Pascals
10: C:DegCelsius
11: Mtr:Meters
0 to 11
0
Programming
Key Selections
o2-01
Local/Remote Key Function
Selection
Local/Remote Key
Determines the status of the Local/Remote key, if
present.
0: Disabled
1: Enabled
Has no function when H/O/A operator is connected.
0 or 1
1
Programming
o2-02
OFF Key Function During Auto
Run
Oper OFF Key
Determines if the off key on the digital operator will
stop the drive when drive is operating from external
terminals or serial communications.
0: Disabled
1: Enabled
0 or 1
1
Programming
o2-03
User Parameter Default Value
User Defaults
Allows storing of current parameter values as a User
Initialization Selection at parameter A1-03.
0: No Change (No user parameter set active).
1: Set Defaults (Saves current parameter settings as user
initialization. A1-03 now allows selecting <1110> for
user initialization.
2: Clear All (Clears the currently saved user
initialization. A1-03 no longer allows selecting
<1110>.
0 to 2
0
Programming
o2-04
Drive/kVA Selection
Inverter Model #
Sets the kVA of the drive. Enter the number based on
drive Model #. Use the
portion of the
CIMR-E7
Model Number.
Reference Appendix B
0 to FF
kVA
Dependent
Programming
o2-05
Frequency Reference Setting
Method Selection
Operator M.O.P.
Determines if the Data/Enter key must be used to input a
frequency reference from the digital operator.
0: Disabled - Data/Enter key must be pressed to enter a
frequency reference.
1: Enabled - Data/Enter key is not required. The
frequency reference is adjusted by the up and down
arrow keys on the digital operator without having to
press the data/enter key.
0 or 1
1
Programming
o2-06
Operation Selection when Digital
Operator is Disconnected
Oper Detection
Determines if the drive will stop when the digital
operator is removed.
0: Disabled - The drive will not stop when the digital
operator is removed.
1: Enabled - The drive will fault (OPR) and coast to stop
when the operator is removed.
0 or 1
1
Programming
o2-07
Cumulative Operation Time
Setting
Elapsed Time Set
Sets the initial value of the elapsed operation timer.
0 to 65535
0 hours
Programming
Denotes that parameter can be changed when the drive is running.
** Factory settings change when b5-01=1 as follows: o1-06=1, o1-07=38, o1-08=24.
Table A.1 Parameter List (Continued
)
Parameter
No.
Parameter Name
LCD Digital Operator Display
Description
Setting
Range
Factory
Setting
Menu
Location
Summary of Contents for E7LBA002
Page 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Page 8: ...Introduction vi Notes ...
Page 12: ...Table of Contents x Notes ...
Page 54: ...Electrical Installation 2 22 Wiring Diagram ...
Page 55: ...Electrical Installation 2 23 ...
Page 87: ...Start Up and Operation 4 9 Notes ...
Page 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Page 248: ...Capacity Related Parameters B 6 Notes ...
Page 279: ...Communications D 27 Note ...
Page 280: ...Communications D 28 ...
Page 292: ...Spare Parts F 6 ...
Page 304: ...Index 12 ...
Page 305: ......