Programming 5 - 25
Definitions:
L = LonWorks Option Card
* = The Drive factory default
J = Native Protocol, Metasys N2
# = The H/O/A selector keys must have AUTO selected
P = Pneumatic Interface (3 to 15 PSIG)
to allow serial com. to control the Drive
U = Native Protocol, APOGEE FLN
@ = Don’t care
V = Native Protocol, Modbus
~ = Jumper required TB5-5 to TB1-12 and TB1-13 to TB5-2
Parameter Reference:
b5-01:
PI Control Selection
H5-02:
Communication Speed Selection
0: Disable (default)
3: 9600 Baud (default)
1: Enable
2: 4800 Baud
H1-03:
Drive Terminal S5 Function Selection
H5-07:
RTS Control Selection
3: Multi-step Ref 1 (default)
0: Disabled (RTS always on)
6C: Com/Inv Sel 2
1: Enabled (RTS on only when sending) (default)
H1-04:
Drive Terminal S6 Function Selection
H5-08:
Communication Protocol Selection
4: Multi-step Ref 2 (default)
0: Modbus (default)
19: PI Disable
1: N2 (Metasys)
H3-08:
Drive Terminal A2 Signal Level
2: FLN (APOGEE)
0: 0 - 10 VDC
d1-01:
Frequency Reference 1
2: 4 - 20 mA (default)
DIP Switch Reference:
S1-1:
Terminating resistor, always on for option L, otherwise on only if last device.
S1-2:
Drive Terminal A2 signal level
On = 4-20 mA Off = 0-10 VDC
S4-2:
Drive input terminal S4 operation
On = Input S4 operates inversely with input S5
Off = Inputs S4 and S5 operate independently
Notes:
Hand mode run/stop for Drive and Bypass is always via the front control panel HAND selector key.
Auto mode run/stop for Drive and Bypass without serial com. is from terminal TB1-2.
Auto mode run/stop with serial com. is from serial com. for both Drive and Bypass modes.
DIP switch configurable terminal TB3-3 is connected to Drive terminal A2 (the default). See Chapter 2 Table 2.8 for the alternate TB3-3 configuration.
A Jumper is required from TB5-2 to TB5-7. This is essential for serial com. applications and benign for all other applications.
Table 5.4 Option Dependent Bypass Parameter Settings with PI Control
Options
Specified
Parameters Effected by Options Specified and
Settings
PCB DIP
Switch S1
1 2
PCB DIP
Switch S4
2
HAND Speed
Command
Source
Drive Terminal A2
Signal Level via TB3-3
or TB5-9
AUTO
b5-01
H1-03
(S5)
H1-04
(S6)
H3-08 H5-2 H5-7 H5-8
Keypad
d1-01
4-20
mA
0-10
VDC
3-15
PSIG
Run/Stop
Speed or
Feedback
Setpoint
Terminal
TB1-2
Serial
#
TB3-3
(A2)
Serial
#
Keypad
Serial
#
PI Control
1
19
@
2
@
@
@
@
On
Off
X
X
X
X
X
PI Control
1
19
@
0
@
@
@
@
Off
Off
X
X
X
X
X
J & PI
1
6C
19~
0
3
1
1
Off
Off
Off
X
X
X
X
X
U & PI
1
6C
19~
0
2
1
2
Off
Off
Off
X
X
X
X
X
V & PI
1
6C
19~
0
3
1
0
Off
Off
Off
X
X
X
X
X
L & PI
1
6C
19~
0
3
0
0
On
Off
Off
X
X
X
X
X
Summary of Contents for E7LBA002
Page 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Page 8: ...Introduction vi Notes ...
Page 12: ...Table of Contents x Notes ...
Page 54: ...Electrical Installation 2 22 Wiring Diagram ...
Page 55: ...Electrical Installation 2 23 ...
Page 87: ...Start Up and Operation 4 9 Notes ...
Page 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Page 248: ...Capacity Related Parameters B 6 Notes ...
Page 279: ...Communications D 27 Note ...
Page 280: ...Communications D 28 ...
Page 292: ...Spare Parts F 6 ...
Page 304: ...Index 12 ...
Page 305: ......