135
Message
System characteristics Cause
Measures
«
30 Flow sensor primary
The heat pump will not
start
Short circuit, air inlet tem-
perature sensor
Check resistance (Pt 500)
at connections 3X1.24
and 3X2.24; replace sen-
sor if required.
«
31 Primary return sens.
The heat pump will not
start
Short circuit - air dis-
charge temperature sen-
sor
Check resistance (Pt 500)
at connections 3X1.23
and 3X2.23; replace sen-
sor if required.
«
32 Evaporator sensor
Short circuit - evaporator
temperature sensor
Check pressure drop
value (type Pt 500) at con-
nections 3X1.5 and
3X2.5; replace sensor if
required.
«
33 Hot gas
Short circuit - hot gas
temperature sensor
Check pressure drop
value (type Pt 500) at con-
nections 3X1.1 and
3X2.1; replace sensor if
required.
«
38 Flow sensor primary
The heat pump will not
start
Break - air inlet tempera-
ture sensor
Check resistance (Pt 500)
at connections 3X1.24
and 3X2.24; replace sen-
sor if required.
«
39 Primary return sens.
The heat pump will not
start
Break - air discharge
temperature sensor
Check resistance (Pt 500)
at connections 3X1.24
and 3X2.24; replace sen-
sor if required.
Troubleshooting
Control unit diagnostics
(cont.)
5414 828 GB
Service
Summary of Contents for VITOCAL 350-A
Page 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Page 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Page 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Page 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...