140
Message
System characteristics Cause
Measures
«
7A Room sensor HC3
■ No frost protection
mode via room temper-
ature sensor
■ No room temperature
hook-up
■ No room temperature
control
Break, room temperature
sensor heating cir-
cuit M3
Check remote control
sensor and replace if
required (see Vitotrol
service instructions).
«
92 Collector sensor
Short circuit, Vitosolic
collector temperature
sensor
Check sensor and replace
if required (see Vitosolic
installation and service
instructions).
«
93 Solar return sensor
Short circuit, Vitosolic
return temperature sen-
sor
Check sensor and replace
if required (see Vitosolic
installation and service
instructions).
«
9A Collector sensor
Break, Vitosolic collector
temperature sensor
Check sensor and replace
if required (see Vitosolic
installation and service
instructions).
«
9B Solar return sensor
Break, Vitosolic return
temperature sensor
Check sensor and replace
if required (see Vitosolic
installation and service
instructions).
A4 Check valve
Solar check valve stuck
or faulty
Inspect check valve and
replace if required (see
Vitosolic installation and
service instructions).
«
A6 Secondary pump
No flow in secondary cir-
cuit (secondary circuit
pump stopped)
Test voltage at connection
2X8.7 and check secon-
dary pump mechanically;
replace if required.
Troubleshooting
Control unit diagnostics
(cont.)
5414 828 GB
Summary of Contents for VITOCAL 350-A
Page 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Page 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Page 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Page 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...