176
Setting how signals "Ext. block-
ing"/"Mixer CLOSE" should affect the
heat pump.
!
Please note
The system may no longer be
protected against frost.
Note
■ Parameter "Ext.blocking/Miclose"
takes priority over "Ext. demand/
Miopen".
■ See also parameter "Set flow temper-
ature for external demand" on
page 193.
Value
Effect
"0"
Heating circuits with mixer M2/M3 – control mode
No heat pump blocking
"1"
Heating circuit with mixer M2 – mixer "CLOSED"
Heating circuit with mixer M3 – control mode
No heat pump blocking
"2"
Heating circuit with mixer M2 – control mode
Heating circuit with mixer M3 – mixer "CLOSED"
No heat pump blocking
"3"
Heating circuits with mixer M2/M3 – mixer "CLOSED"
No heat pump blocking
"4"
Heating circuits with mixer M2/M3 – control mode
Heat pump blocking
"5"
Heating circuit with mixer M2 – mixer "CLOSED"
Heating circuit with mixer M3 – control mode
Heat pump blocking
"6"
Heating circuit with mixer M2 – control mode
Heating circuit with mixer M3 – mixer "CLOSED"
Heat pump blocking
"7"
Heating circuits with mixer M2/M3 – mixer "CLOSED"
Heat pump blocking
Menu
■
"Device settings"
■
"Programming"
■
"System definition"
■
"Ext.blocking/Miclose"
Delivered condition
4
Setting
0 to 8
System definition control settings
External blocking/mixer "CLOSED"
5414 828 GB
Summary of Contents for VITOCAL 350-A
Page 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Page 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Page 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Page 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...