97
2X7.1
2X7.2
A
1X3.1
1X2.N
C
B
K1
D
A
Terminals on PCB 2: Contact load
230 V~, 4(2) A, zero volt contact
B
Transfer jumper from 1X3.1 (PCB 1)
to 2X7.1 (PCB 2)
C
Connection at the external heat
source on the terminals for external
demand
D
High limit safety cut-out (this is set
to 70 °C) as heat pump protection
K1 Relay; sizing in accordance with the
external heat source; observe
safety instructions
Appliance
Connection
Required parameters:
Parameter
Ó
setting
Mixer motor, external heat
source
2X7.7
V
OPEN
1X1.
?
1X2.N
2X7.8
v
CLOS
"Ext. heat source"
■
"Ext. heat source"
Ó
"Yes"
Control of an external heat
source
2X7.1
2X7.2
(see page 43)
"Ext. heat source"
■
"Ext. heat source"
Ó
"Yes"
Circulation pump for DHW
reheating
Note
Not possible in conjunction with
an immersion heater EHE for a
DHW cylinder (see
pages 34, 48)
2X8.13
1X1.
?
1X2.N
(see page 44)
"Ext. heat source"
■
"Ext. heat source"
Ó
"Yes"
External hook-up
The external components can also be hooked up via "External extension H1".
Installation sequence
Electrical connections in the heat pump control…
(cont.)
5414 828 GB
Installation
Summary of Contents for VITOCAL 350-A
Page 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Page 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Page 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Page 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...