103
L
Input for central fault message
facility, lag appliance
Open contact 1X3.10/1X3.11 trig-
gers a message (see central fault
message, page 99).
Required parameters (code to be entered by "Contractor": 5243)
Appliance
Parameter
Ó
setting
Lead appliance
"System definition"
■
"System diagram"
Ó
"0"
to
"10"
■
"Ext. extension"
Ó
"Yes"
■
"Cascade control"
Ó
"1"
■
"Output lag heat pump"
Ó
"0"
to
"255"
(see
■
"No. of ext. heat p"
Ó
"1"
to
"3"
(see
Lag appliance
Note
Set these parameters for all lag
appliances.
"System definition"
■
"System diagram"
Ó
"11"
■
"Cascade control"
Ó
0
■
"Set flow ext. demand"
Ó
"0"
to
"70"
(see
Installation sequence
Electrical connections in the heat pump control…
(cont.)
5414 828 GB
Installation