164
3.
Hydraulically balance the connected
heating circuits.
4.
Check the outside temperature sen-
sor (see page 166).
5.
Increase the set room temperature
for standard mode and match the
heating curves.
Operating instructions
6.
Enable heating operation via the inte-
gral instantaneous heating water
heater (if installed) (see page 189).
No programming unit display
1.
Switch ON system ON/OFF switch.
2.
Check heat pump control unit fuse;
replace if required (see page 167).
3.
Check whether there is power at the
heat pump control unit; switch ON
power supply if required.
4.
Check the plug-in and threaded con-
nections.
5.
Replace programming unit if
required.
6.
Replace PCB 2 (main PCB) if
required.
Troubleshooting
Measures in case the room temperature is…
(cont.)
5414 828 GB