120
0
1.
Open any on-site non-return valves
installed.
0
2.
Check the pre-charge pressure of
the expansion vessel (see
page 120).
0
3.
Thoroughly flush the on-site pipe-
work.
0
4.
Fill the heating circuit with water via
the on-site drain & fill valve; while
doing so, check the system pres-
sure at the pressure gauge.
Minimum system pressure: 0.8 bar
Permiss. operating pressure: 3 bar
0
5.
Close drain & fill valve.
0
6.
Open manual air vent valve
B
.
0
7.
!
Please note
To prevent equipment dam-
age, check the flow and
return connections of the
secondary heat pump circuit
for
leaks
.
In case of leaks, immediately
shut off the equipment, drain
the water and check the
seating of the seal rings.
Replace all seal rings that
may have become dis-
lodged.
0
8.
Set the operating mode selector to
"
9
".
0
9.
Switch ON the power.
10.
Close manual air vent valve
B
after
complete venting.
11.
Check the system pressure and top
up with water if required.
Checking the expansion vessel and the heating circuit pressure
Carry out this test on a cold system.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5414 828 GB
Summary of Contents for VITOCAL 350-A
Page 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Page 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Page 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Page 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...