Message
System characteristics Cause
Measures
D3 Low pressure
Low pressure fault
■ Heat pump faulty
■ Fan faulty or air ducts
blocked
■ Low pressure sensor
faulty
■ Have heat pump tested
by a refrigeration engi-
neer.
■ Check fan and shut-off
facilities; clean air ducts
if required.
Check low pressure sen-
sor, lead and EEV control-
ler. If required, check
whether jumper in plug
aYH
between terminal 3
and 4 is fitted (switching
signal can be tested at ter-
minal 1X5.7 (230 V) and
must be continuously
active if a pressure sensor
is installed).
Troubleshooting
Control unit diagnostics
(cont.)
5414 828 GB
Service