241
Setting and test values
Set value
Commission-
ing
Testing the external heating circuit pumps
Circulation pump type
Circulation pump stage
Overflow valve setting
Primary circuit commissioning
Air inlet temperature
°C
Air discharge temperature
°C
Temperature differential ΔT:
Secondary circuit flow temperature = 35 °C
at air inlet temperature
≤
15 °C
K
4 to 8
Secondary circuit flow temperature = 35 °C
at air inlet temperature > 15 °C
K
4 to 13
Testing the mixer, heat pump and cylinder heating
– tested under the following
conditions:
Room temperature
°C
Outdoor temp.
°C
"
DHW cylinder top
" temperature constant?
Yes (±1 K)
Secondary circuit flow temperature
°C
rising
from:
to:
Temperature differential ΔT
"
Secondary flow
" / "
Secondary return
"
6 to 8 K
Control parameters report
Parameter
Page
Setting range Delivered
condition
Commission-
ing
System definition
System scheme
0 to 11
(page 30)
2
Language
Deutsch
Temp. diff. heating
0 to 20 K
4 K
Swimming pool
Yes/No
No
Cascade control:
Lead appliance
0 to 2
0
Lag heat pump
0 to 2
0
No. of external heat
pumps
1 to 4
0
Output lag heat pump
0 to 255 kW
10 kW
External extension
Yes/No
No
Commissioning/service reports
Hydraulic parameters report
5414 828 GB
Service
Summary of Contents for VITOCAL 350-A
Page 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Page 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Page 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Page 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...