![Viessmann VITOCAL 350-A Installation And Service Instructions Manual Download Page 242](http://html.mh-extra.com/html/viessmann/vitocal-350-a/vitocal-350-a_installation-and-service-instructions-manual_1016791242.webp)
242
Parameter
Page
Setting range Delivered
condition
Commission-
ing
Op. mode change HC
0 to 11
11
Op mode change eff.
0 to 3
2
Op. mode change time
0 to 12 h
8 h
Ext.demand/Miopen
0 to 7
4
Ext.blocking/Miclose
0 to 8
4
Ext. blocking effect
0 to 31
0
Vitosolic type
0 to 2
0
Vitocom 100
Yes/No
No
Wtimer DHW Circ.
(DHW circulation pump)
Compressor
Enable
Yes/No
Yes
Output
1 to 255 kW
10 kW
Defrost stop tempera-
ture
0 to 70°C
15 °C
External heat source
Ext. heat sources
Yes/No
No
Priority
Yes/No
Yes
Dual-mode temperature 182
-50 to 50 °C
10 °C
Ext. HS for DHW
Yes/No
No
DHW
DHW cylinder temp
10 to 70 °C
50 °C
Switching times DHW
Min. temperature
5 to 60 °C
10 °C
Max. temperature
20 to 80 °C
60 °C
Hysteresis
1 to 10 K
7 K
Hyst. booster heater
2 to 30 K
10 K
Start optimisation
Yes/No
No
Stop optimisation
Yes/No
No
Auxiliary function
Yes/No
No
Set temperature 2
10 to 70 °C
60 °C
Temperature sensor 2
Yes/No
No
Booster heater
Yes/No
No
DHW with e heating
Yes/No
Yes
Commissioning/service reports
Control parameters report
(cont.)
5414 828 GB
Summary of Contents for VITOCAL 350-A
Page 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Page 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Page 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Page 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...