Above the dual-mode temperature, the
heat pump control unit only starts the
external heat source if, for example, a
heat pump fault is present.
Menu
■
"Device settings"
■
"Programming"
■
"Ext. heat source"
■
"Dual-mode temperature"
Delivered condition
10 °C
Setting
–50 to +50 °C
External heat source for DHW
Using the external heat source for DHW
heating.
If the heat demand of the DHW cylinder
cannot be covered by the heat pump, the
circulation pump for DHW reheating and
the external heat source will be activa-
ted.
Note
With setting "Yes", no immersion heater
EHE (accessory) in the DHW cylinder
can be controlled (see page 187).
"Yes"
External heat source is ena-
bled for DHW heating.
"No"
External heat source is
blocked for DHW heating.
Menu
■
"Device settings"
■
"Programming"
■
"Ext. heat source"
■
"Ext. HS for DHW"
Delivered condition
No
Setting
Yes/No
Control settings, external heat source
Dual-mode temperature
(cont.)
5414 828 GB
Service
Summary of Contents for VITOCAL 350-A
Page 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Page 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Page 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Page 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...