![Viessmann VITOCAL 350-A Installation And Service Instructions Manual Download Page 96](http://html.mh-extra.com/html/viessmann/vitocal-350-a/vitocal-350-a_installation-and-service-instructions-manual_1016791096.webp)
96
For further information, see from
page 104.
Immersion heater EHE
Connection
Installation instructions, immersion heater EHE
Appliance
Connection
Required parameters:
Parameter
Ó
setting
Immersion heater EHE
2X8.13
1X1.
?
1X2.N
(see page 48)
"DHW"
■
"Booster heater"
Ó
"Yes"
Note
Alternatively, an external heat source
can be installed on site for DHW heat-
ing.
External heat source
!
Please note
Protect the heat pump against
temperatures over 70 °C from the
external heat source.
Install a high limit safety cut-out
or take further measures if
required.
Note
■ The switching contact to demand heat
from an external heat source in the
heat pump ("Ext. HS for DHW") is a
zero volt N/O contact that closes in
case of heat demand.
■ This contact can be subjected to a load
of 230 V~/4(2) A in case of an external
voltage supply. Never route low volt-
age via this contact; that requires an
on-site relay.
■ The boiler water temperature sensor in
the external heat source (identification
F20; terminal 3X1.4/3X2.4) must cap-
ture the average temperature of the
external heat source.
Installation sequence
Electrical connections in the heat pump control…
(cont.)
5414 828 GB
Summary of Contents for VITOCAL 350-A
Page 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Page 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Page 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Page 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...