Message
System characteristics Cause
Measures
«
CF Communication module
Communication error -
LON module in heat
pump control unit
Check LON communica-
tion module and replace if
required.
If required, replace in the
following order: PCB 3,
ribbon cables between
PCB 3 and 2, PCB 2.
«
D1 Compressor
Compressor fault:
Thermal compressor
relay or safety element of
full wave soft starter (if
installed) has respon-
ded.Separate compres-
sor motor protection (if
installed) has responded
■ Reset compressor ther-
mal relay, check setting,
restore delivered condi-
tion (
"Reset"
, see oper-
ating instructions).
Check compressor
electrical connections,
test coil resistance of
compressor motor.
Check compressor
phase sequence.
The switching signal (of
thermal relay, full wave
soft starter, separate
motor protection) can
be tested at terminal
1X5.9 (230V).
Note
If overheating occurs,
internal motor protection
prevents a re-enabling of
the compressor for 1-3
hours.
■ If required, replace full
wave soft starter (if
installed); have com-
pressor checked by
refrigeration engineer.
Troubleshooting
Control unit diagnostics
(cont.)
5414 828 GB
Summary of Contents for VITOCAL 350-A
Page 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Page 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Page 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Page 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...