122
Setting the control parameters
1.
Enable the
"Contractor"
level. For
information regarding the
"Contrac-
tor"
level and control parameters,
see chapter "Control settings" from
page 168.
2.
Check the control settings using the
details regarding the delivered condi-
tion (from page 241).
Record only modified values in the
service report from page 241.
3.
Acknowledge all messages (see
page 132).
Note
Messages are displayed by manually
controlling some components during
commissioning. These do not indi-
cate appliance faults.
Commissioning assistant
The commissioning assistant guides you
through the commissioning in nine steps.
Scans, checks and corrections can be
made.
Function
Explanation
1.
Language selection
Selecting the required language
Note
When the unit is first commissioned, the display
is in German:
Sprache
Deutsch
English
Nederlands
Svenska
ZURÜCK
Français
Italiano
Suomi
Polski
OK
2.
Safety scan
Check whether the commissioning assistant
should be started
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5414 828 GB
Summary of Contents for VITOCAL 350-A
Page 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Page 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Page 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Page 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Page 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...